Installation

SmartCell Wireless Fire Control Panel

The SmartCell Wireless Fire Control Panel is the central control unit for the SmartCell wireless fire detection system, providing a flexible, professional solution for smaller commercial properties, residential applications and other buildings where a conventional hardwired fire alarm installation may be disruptive or impractical.

SmartCell uses robust 868–870 MHz wireless communication, avoiding the extensive cabling normally associated with a conventional fire alarm system. The system provides two-way communication between the control panel and wireless devices, with faults and low-battery conditions reported back to the panel.

The system can incorporate SmartCell smoke and heat detectors, sounders, visual alarm devices, manual call points and other wireless devices, allowing a system to be designed around the requirements of the property. SmartCell supports up to 32 fire devices, with the wider system capable of supporting up to 64 devices when information devices are included.

Designed for professional installation

The SmartCell control panel is not a standalone smoke alarm. It forms the central component of a complete wireless fire detection system and must be correctly designed, configured and commissioned with compatible SmartCell devices.

For this reason, we recommend purchasing the panel together with professional installation and system design advice from Safe & Smart.


Key features

  • Fully wireless fire detection system
  • Supports up to 32 fire devices
  • Up to 64 devices across the wider SmartCell system, including information devices
  • 16 fire/information zone indicators
  • Compact surface-mounted control panel
  • 80-character OLED display
  • Two-way wireless communication
  • 868–870 MHz operating frequency
  • Integrated mains power supply
  • 6V 4Ah standby battery
  • Optional communications module for remote connectivity
  • Suitable for SmartCell wireless smoke, heat, sounder, beacon and call-point devices
  • Designed for fast installation with minimal disruption
  • Suitable for small to medium-sized fire detection installations

Technical specifications

Specification SmartCell Wireless Control Panel
Model SC-11-1201-0001-99
System type Wireless fire detection control panel
Maximum fire devices 32
Maximum system capacity Up to 64 devices including information devices
Zone indicators 16
Display 80-character OLED
Power supply 230V AC
Operating voltage 220–240V AC, 50Hz
Rated current 0.3A
Standby battery 6V 4Ah
Wireless frequency 868–870 MHz
Transmitter power 14dBm max / 25mW
Dimensions 275 × 220 × 80mm
Weight 1.55kg
Mounting Surface mount
Cable entries 4 × 100mm bottom / 4 × 100mm rear
Operating temperature -5°C to +45°C
Maximum relative humidity 95%, non-condensing
Environment Indoor
IP rating IP30
Standards EN54-2, EN54-4, EN54-13, EN54-25
Certification CE / CPR

Technical specifications are taken from the SmartCell product documentation.


🔌 Optional communications

The SmartCell panel can accommodate an optional communications module, allowing the system to be connected for remote services and alarm routing.

SmartCell's remote services can provide features such as remote configuration and system information, while suitable communications equipment can also be used for connection to an Alarm Receiving Centre where required.

Communications modules are not included with this panel unless specifically stated.


Professional installation

SmartCell installation — best estimate £500.00 inc VAT

We offer professional installation and commissioning of SmartCell systems.

The £500.00 inc VAT installation price is a best estimate for a straightforward installation and is subject to survey.

The final installation cost will depend on:

  • Number of detectors and other devices
  • Property size and layout
  • Number of zones required
  • Panel location
  • Mains supply requirements
  • System configuration
  • Access
  • Commissioning requirements
  • Any additional equipment required

Hardwired electrical work and more complex installations are subject to survey.

If the survey identifies additional requirements that change the installation price, we'll explain these to you before carrying out the work.


Why choose SmartCell?

Traditional wired fire alarm systems can require significant cable installation, disruption and making-good. SmartCell's wireless architecture can significantly simplify installation while providing a professional, standards-based fire detection system.

Its wireless communication operates in the 868–870 MHz band and is designed specifically for wireless fire systems rather than relying on ordinary Wi-Fi. SmartCell states that its wireless system is designed to meet the requirements of EN54-25 for wireless fire detection systems.


Important

This product is a control panel and is not a complete fire alarm system by itself.

A suitable system requires compatible SmartCell devices and professional design, configuration and commissioning appropriate to the property.

For advice on designing a SmartCell system for your home or business, contact Safe & Smart before purchasing.


You may also like